TC de núcleo dividido, 200 A, 200 A: 26,6 mA, diámetro del orificio de 15 mm (0,6"), ESCT-015-200UL

$60.00

descripción
TC de núcleo dividido, 200 A, 200 A: 26,6 mA, diámetro de orificio de 25 mm, hasta Tamaño de cable aislado 1/0 ESCT-015-200UL
View More

More information

Tipo de CT: núcleo partido

máx. Amperaje: 200 amperios

Diámetro interior: 15 mm o 0,6 pulgadas

Diámetro exterior: 45,5 mm o 1,75 pulgadas

Espesor: 18,5 mm o 0,75 pulgadas

Modelo: ESCT-015-200UL

Certificaciones: Aprobado por UL para su uso con nuestros omnímetros listados en UL

Calibre del cable: Para uso en alambre de tamaño 1/0 o más pequeño. Es mejor medir el diámetro de su cable en milímetros, en lugar de usar el calibre AWG. Esto se debe a que el grosor del aislamiento varía considerablemente de un fabricante de cables a otro. Es mucho mejor sobredimensionar su CT que subdimensionarlo.

Estos CT de núcleo dividido de 15 mm son fáciles de instalar: simplemente encaje estos transformadores de corriente alrededor de los cables que se están leyendo. Son muy compactos y pueden medir la corriente utilizada en la mayoría de los sistemas eléctricos residenciales. Estos CT están diseñados para usarse junto con nuestra línea Omnimeter de medidores eléctricos para cualquier carga de 1/4 amperio a 200 amperios.

Estos TC son tan fáciles de instalar que puede ver un ahorro general en costos de mano de obra reducidos para compensar el aumento del precio del formato de núcleo dividido.

Estos son muy compactos y económicos por su nivel de precisión (0.1% que son solo unos pocos vatios). Tienen 7518 vueltas internas, creando una salida de 26,6 mA como máximo. amperaje.

Los TC encajarán en cables aislados de hasta 400 MCM. Es una buena idea medir sus cables antes de seleccionar un modelo CT para asegurarse de que encajarán.

  • Use 1 CT para sistemas norteamericanos monofásicos de 120 voltios o extranjeros de 230 voltios y 2 hilos
  • Use 2 CT para sistemas monofásicos de 120/240 voltios
  • Utilice 2 TI para sistemas trifásicos de 3 hilos (sin neutro)
  • Use 3 CT para sistemas trifásicos de 4 hilos

Estos CT son reconocidos por UL y cUL y están aprobados para su uso con nuestros medidores listados por UL, para ser una instalación completa de medidores listados por UL.

Cada CT tiene un número de serie único, se prueba individualmente e indica la orientación correcta del CT en relación con la carga del sistema eléctrico que se mide.

Para obtener más información sobre nuestros productos y servicios, lo alentamos a que visite nuestra Base de conocimientos en línea, que proporciona hojas de especificaciones, videos, tutoriales, preguntas frecuentes, diagramas y más.

Hoja de especificaciones: ESCT-015-200UL Hoja de especificaciones




  • 5 stars: 4 (100%)
  • 4 stars: 0 (0%)
  • 3 stars: 0 (0%)
  • 2 stars: 0 (0%)
  • 1 star: 0 (0%)
R
Richard Nordstrom
Sub metering a transmission shop

Multiple units sharing a meter from another unit best way to pay for use except on thr demand part of time of use

M
Mark Weaver
Works perfectly.

The CTs work perfectly.

I recommend an assortment of locking bushings be included to clamp the CTs securely against the primary cable to prevent the CT falling against other components. I used cut 1/2" and 3/4" bushing with zip-ties to do this, but a designed product might work better.

J
James Clark
A well thought out solution to power management

This compact system worked as advertised right out of the box.
I did have to tell McAfee to get lost, as it thought that this SW was a virus pit.
G-Data likes the software just fine :)
My application is for load shedding. That is, real-time monitoring of the current load on the incoming service lines, with relay control to disconnect loads that are basically optional (e.g. disconnect the EV charger).
Software downloaded easily and immediately began communication with
the meter over a 42' twisted-pair RS-485 link to the Dash software program.
Data export to Excel is straightforward.
I did have to use a Dremel tool to very lightly trim the CT's to fit around the
main lines into the Service Entrance. That said, I definitely appreciate the
compactness of the CT's they use ( mine are CT-200's )
My only complaint at this point is that I cannot arbitrarily set the beginning and ending temporal points for data export. Seems to be all or nothing.

J
Jeff Ditter
3 phase phase metering equipment

Great equipment and easy installation. The youtube video was spot on. Thanks for a great product.

R
Ruben Vidal

Why does your diagram show only using two CT’s for metering a 3 phase panel and jumping from 8 to 10 on your diagram

EKM Metering Inc.

If you are using an EKM Omnimeter to meter a 3-phase 3-wire system, you only need to use 2 current transformers. Here is a page that describes how to meter this system: https://help.ekmmetering.com/support/solutions/articles/6000081678-3-phase-3-wire-metering-up-to-600-volts

The reason you only need 2 Current Transformers for a 3-phase 3-wire system has to do with what is called "Blondel's theorem”:
http://en.wikipedia.org/wiki/Blondel's_theorem

This essentially says that the number of CTs you need to use to meter a given system is the number of hot wires plus the neutral wire, minus 1.

# of CTs = # hot wires + 1 if there is a neutral -1

Therefore if you have 2 wires: you only need 1 CT, 3 wires: you only need 2 CTs, 4 wires: you need 3 CTs.

H
Harry Chaisson

Does it come with a digital read out?

EKM Metering Inc.

Our current transformers are meant to be paired with our EKM Omnimeters. If you were to only buy this ESCT-015-200UL CT it would not come with anything else, so would not be useful by itself in most cases. The CTs and the Omnimeters are sold separately.

You will need either 1, 2, or 3 CTs per Omnimeter depending on your electrical system:

- Use 1 CT for 120 volt 2-wire systems (or foreign 230 volt 2-wire systems).
- Use 2 CTs for a 120/240V three-wire system (two hots and a neutral, with or without ground).
- Use 2 CTs for 3-phase 3-wire systems.
- Use 3 CTs for 3-phase 4-wire systems.

E
Ernest Montllo

Hi, is this current sensor IP65 or higher rated. Can it be used for outdoors? Thanks

EKM Metering Inc.

No, this CT model is not IP65 rated and is not suitable for outdoor use. For an outdoor CT model I recommend our OSCT-063x033-800 (https://www.ekmmetering.com/collections/current-transformers-cts/products/outdoor-split-core-ct-800a), which is IP65 rated and will work on electrical systems that are 800A or less.