Split-Core CT, 200A, 200A:26.6mA, 25mm (0.98") Hole Diameter, SCT-025-200UL

$104.00

description
Split-core CT, 200A, 200A:26.6mA, 25mm Hole Diameter, up to 400 MCM insulated wire size SCT-025-200
View More

More information

CT Type: Split-Core

Max. Amperage: 200 amps

Inside Diameter: 25 mm or 0.98 inches

Outside Diameter: 70 mm or 2.76 inches

Thickness: 18 mm or 0.71 inches

Model: SCT-025-200UL

Certifications: CE, Approved by UL for use with our UL Listed Omnimeters

Wire Gauge: For use on cable that is 400 MCM or smaller. It is best to measure your wire diameter in millimeters, rather than use the MCM wire size. This is because the insulation thickness varies materially from one wire manufacturer to the next. It is much better to oversize your CT than to undersize it.

These 25mm Split Core CTs are easy to install: simply snap these current transformers around the wires being read. They are very compact and can measure the current used in the majority of residential electrical systems. These CTs are designed to be used in conjunction with our Omnimeter line of electric meters for any load from 1/4 amp to 200 amps.

These CTs are so easy to install you may see an overall savings in reduced labor costs to offset the increased price of the split core format.

These are very compact and economical for their level of accuracy (0.1% which is just a few watts). They have 7518 internal turns, creating a 26.6 mA output at max. amperage.

The CTs will fit on up to 400 MCM insulated wires. It is a good idea to measure your wires before selecting a CT model to be sure that they will fit.

  • Use 1 CT for 120 volt single phase North American, or 230 volt 2-wire foreign systems
  • Use 2 CTs for 120/240 volt single phase systems
  • Use 2 CTs for 3-phase 3-wire systems (no neutral)
  • Use 3 CTs for 3-phase 4-wire systems

These CTs are UL and cUL Recognized and are approved for use with our UL listed meters, to be a complete UL Listed meter install.

Each CT has a unique serial number, is individually tested, and indicates the correct orientation of the CT in relation to the load of the electrical system being metered.

For more information about our products and services, we encourage you to visit our online Knowledge Base, which provides spec sheets, videos, tutorials, FAQs, diagrams, and more.

Spec Sheet: Split Core, 25mm, 200A CT

  • 5 stars: 11 (100%)
  • 4 stars: 0 (0%)
  • 3 stars: 0 (0%)
  • 2 stars: 0 (0%)
  • 1 star: 0 (0%)
J
Joseph
Meters for my apartments

We installed another EKM METERING system at one of my 4 unit apartment buildings. It was an easy installation and the products are very reliable!

T
Tony F.
Works first time, every time

best equipment in the business.

j
joe kersey

easy intall

Z
Ziad Abdurahman
Great product

Great product and good service

J
John

Really like EKM

C
Charles Beck
Easy to setup and very handy

Equipment was all very easy to install and the EKM team provided great tech support along with equipment solutions to our job

G
George Gibbs
Well engineered!

Our customer (a commercial property manager) was stymied over how to add energy used by a remote fire alarm power center to the existing common area EKM sub-meter. Josh at EKM got us looking like a "knight-in-shining-armor" when he advised how to employ a split-core CT (current transformer) to do the trick! Just spliced it into the original CT circuit per his instructions, oriented the CT toward the load, and everything worked perfectly. By the way, the arrow on the side of the CT points toward the load. Made it so simple to correctly orient the direction of current flow through the CT. Thanks josh!

B
Brian Miller
CT

Easy to install and the instructions were easy to follow

R
Robert Douglas
Great product

Equipment was all very easy to install and the EKM team provided great tech support along with equipment solutions to our job

P
Paul Bianchi

CTs worked perfectly

P
Pete Sabo
Purchase

Fast and Easy

S
Steve Kowalske

Will Split-core CT, 200A, 200A:26.6mA, 25mm (0.98") Hole Diameter, SCT-025-200UL
Work with any meter I purchased from you?

EKM Metering Inc.

All of our CTs will work with any of our Omnimeter models only. 

Note that if you purchase the meter separately from the CTs, contact us and let us know so we can preprogram the meter to work with those CTs before we ship it out to you.

Note that if you already have one of our Omnimeter models, and want to add these particular CTs to it, it may need to be programmed to work with these CTs if it was shipped originally with CTs that were not for 200A (our 400A or 600A CTs, for instance). For more assistance, contact us directly here: https://www.ekmmetering.com/pages/contact-us

M
MIGUEL CORTES

would this meter work with standard CT's ratio 200:5 or 400:5

EKM Metering Inc.

200:5 and 400:5 are for 5 amp output Current Transformers.  These will not work with our EKM Omnimeters.  Our Omnimeters are designed to work with 26.6mA output CTs.  So attaching 5 amp output CTs would not be at all accurate and could damage the Omnimeter.
We chose to design our meters for 26.6mA output CTs because they are more accurate, particularly when it comes to phase angle measurement.

W
Walter Rowntree

do these CT's output 333.33 mV at max rated input current?

EKM Metering Inc.

Thanks for our inquiry. Our CTs output 26.6mA at max rated input current. These work with our Omnimeter models. They will not work with third party devices that require 333.33 mV.